Distributed temperature measurements on a u-pipe thermosyphon borehole heat exchanger with CO2

published May 04, 2012 - 8 pages

In thermosyphon Borehole Heat Exchangers, a heat carrier fluid circulates while exchanging heat with the ground without the need of a circulation pump, representing an attractive alternative when compared to other more conventional systems. Normally, the fluid is at liquid-vapor saturation conditions and circulation is maintained by density differences between the two phases as the fluid absorbs energy from the ground. This paper presents some experimental experiences from a 65 meter deep thermo

In thermosyphon Borehole Heat Exchangers, a heat carrier fluid circulates while exchanging heat with the ground without the need of a circulation pump, representing an attractive alternative when compared to other more conventional systems. Normally, the fluid is at liquid-vapor saturation conditions and circulation is maintained by density differences between the two phases as the fluid absorbs energy from the ground. This paper presents some experimental experiences from a 65 meter deep thermosyphon borehole heat exchanger loop using Carbon Dioxide as heat carrier fluid, instrumented with a fiber optic cable for distributed temperature measurements along the borehole depth. The heat exchanger consists of an insulated copper tube through which the liquid CO2 flows downwards, and a copper tube acting as a riser. The results show temperatures every two meters along the riser, illustrating the heat transfer process in the loop during several heat pump cycles.