A UK first: CO2 for a hospital catering facility

By R744.com team, Sep 13, 2010, 08:55 2 minute reading

The design and installation has just been completed on what was to become the first hospital catering facility refrigeration system to run with CO2 in the UK. + IMAGE GALLERY

A CO2 unit supplied by Green & Cool has been installed and commissioned by CCS Refrigeration, through principle contractor Aggora on behalf of Compass Group, trading as Medirest to provide for the on site catering requirements of patients, restaurant and hospital staff at the Homerton University Hospital in London, UK.

The water supply for the large CO2 chiller coldroom is run from the existing ammonia chillers supplied by J & E Hall and installed some 75 metres away. The complete system, hence, runs on natural refrigerants, with the ammonia system chilling water and CO2 cooling the evaporators.

The system

The two existing ammonia chiller units each with 0.5 MW cooling capacity, which cool water from 12°C to 6°C, enabled the design of a sub-critical system. Nonetheless, due to the relatively high condensing temperature, CCS Refrigeration required trans-critical compressors even though the system would run sub-critically year round.

Swedish CO2 refrigeration specialist Green & Cool provided a CO2 unit built in the specifications of CCS. The overall system features:
  • Baltic DO23MT CO2 trans-critical unit by Green & Cool, with a 100% back up twin compressor system
  • Water-cooled plate heat exchanger
  • Green & Cool CO2 control system, with user-friendly touch screen
  • Danfoss AKVH pulse valves
  • Searle kecx-70L evaporators
  • Leak detectors in the coldroom by CPC: the leak detection system was installed first prior to commissioning and features a battery back up in case of power failure.
  • Coldroom controls provided by RDM
  • LED tube lighting
  • e-cubes to the air on probes

Energy and emissions savings

Significant energy savings associated with the new system was the reason behind opting for it.

The energy savings over a conventional system have been calculated to be 16.7% over the course of one year, not including the savings from the installed LED lighting or fitted e-cubes. LED tube lighting is again very energy saving. Finally, by installing e-cubes to the air on probes a further 15% energy savings are realised compared to when conventional probes reading air temperature are being used.

Over a ten year lifespan, some 628,000 kg of CO2 emissions will be saved thanks to the use of a CO2 system and compared to a standard HFC system.

More CO2 projects in the pipeline by CCS

CCS have a number of CO2 projects on the books at the moment, with Café Royal London and Kapsarc SA to name a few.


Contact Information

If you would like to contact Green & Cool for any enquiries, you may send a request to Stig-Göran Lind directly.

If you would like to contact Danfoss for any enquiries, you may send a request to Anatolii Mikhailov directly.

MORE INFORMATION

By R744.com team (@r744)

Sep 13, 2010, 08:55




Related stories

Sign up to our Newsletter

Fill in the details below